How Does a Pressurisation Unit Work? Expansion Vessels Explained
A pressurisation unit keeps a sealed heating or chilled water system filled to the right pressure. When the pressure drops, its pump tops the system up from a small break tank and when the pressure is right it stops.
It works hand in hand with an expansion vessel, which soaks up the extra volume as the water heats and gives it back as the water cools. Together they keep the system pressure steady, which protects the boilers, pumps and pipework.
Most commercial buildings, schools, hotels and apartment blocks with sealed heating systems have a pressurisation unit in the plant room. NT Cloke Pumps & Water installs, services and repairs them every week, so here is a plain guide to how they work and what to look out for.
What is a pressurisation unit?
Older heating systems were open vented. A feed and expansion tank in the loft or on the roof kept the system topped up by gravity and gave the water somewhere to go as it expanded.
Most modern commercial heating and chilled water systems are sealed instead. They run at a higher pressure, which suits taller buildings and modern boilers, but they need something to keep them filled. That is the job of the pressurisation unit.
A typical unit has:
- A break tank, which is filled from the mains and keeps the heating water separate from the drinking water supply.
- One or two pumps, which push water from the break tank into the heating system.
- A pressure sensor and control panel, which watch the system pressure and switch the pumps on and off.
- Alarms for low and high pressure, which can be linked to the building management system.
How does a pressurisation unit work?
The control panel is set with a pressure range that suits the building. When the system pressure falls to the lower setting, for example after a small leak, after air has been bled off or as the system cools, the pump starts and adds water from the break tank. When the pressure reaches the upper setting the pump stops.
The break tank has an air gap between the mains inlet and the water inside, so heating water can never flow back into the drinking water supply. That is why a pressurisation unit is the right way to fill a commercial sealed system, rather than a hose or a filling loop left open.
If the pressure drops too low or rises too high, the unit raises an alarm and can shut down the boilers to protect them. Many units also count how often they top up, which is a useful early warning of a leak somewhere in the system.
What does the expansion vessel do?
Water expands as it heats up. In a sealed system that extra volume has to go somewhere, otherwise the pressure would climb until the safety valve opened.
The expansion vessel is a steel tank split in two by a rubber diaphragm or bag. One side connects to the heating system and the other side holds air or nitrogen at a set pressure, called the pre-charge. As the water heats and expands it pushes into the vessel and squeezes the air. As it cools, the air pushes the water back out.
When the vessel is working, system pressure stays steady and the pressurisation unit only needs to top up now and then. When the diaphragm fails or the vessel loses its pre-charge, the pressure swings up and down, the safety valve may discharge water and the unit keeps refilling the system. That constant fresh water brings in oxygen, which speeds up corrosion.
Booster sets use expansion vessels too, on the cold water side, to stop the pumps starting and stopping too often. In Haverhill we fitted a new pressure vessel and bearing kit to bring a booster set back to smooth running.
Single pump or twin pump units?
Smaller systems often use a single pump unit. For larger buildings and anywhere that cannot afford to lose its heating we recommend a twin pump unit. The two pumps share the work and if one fails the other carries on.
At a busy student block in Cardiff a pump and controls failure left the pressurisation unit unable to hold pressure. With term about to start, we installed a new Mikrofill twin pump pressurisation unit without any downtime.
What are the signs of a pressurisation unit problem?
Call an engineer if you notice:
- Low pressure alarms or the boilers locking out on low pressure.
- The pump on the unit running much more often than it used to.
- System pressure rising a lot as the heating warms up.
- Water coming out of the safety valve.
- The break tank overflowing or running dry.
- A noisy or leaking pump on the unit.
- The unit switched off or bypassed. This one matters most, because the system then has no protection at all.
At a coastal college a bypassed pressurisation unit let the heating system run at low pressure until several heating pumps ran dry. We replaced 10 mechanical seals and reinstated the unit so the pumps were protected again.
How often should a pressurisation unit be serviced?
We recommend a service at least once a year, ideally before the heating season. A service should include:
- Checking and resetting the expansion vessel pre-charge.
- Checking the pressure settings and alarms.
- Testing the pumps, pressure sensor and controls.
- Cleaning and checking the break tank and its float valve.
- Looking at the top-up records for signs of a leak.
New units also need setting up properly. On a London building site our engineers carried out the full commissioning of a new pressurisation unit, checking the pipework, pressures, expansion and alarms before signing it off.
Need help with a pressurisation unit?
Whether your unit keeps alarming, your expansion vessel needs checking or you need a new unit fitted, our engineers work on Mikrofill, Grundfos, Flamco and every other major make. At a Leicester school we replaced a failed unit with a new Mikrofill 3 and commissioned it during term time.