The Challenge
Our engineers were called to a busy restaurant in Cardiff city centre where a single pump booster set was running continuously and failing to shut down.
This constant operation was a clear warning sign. Left unresolved, it would have led to premature pump wear, increased energy use and a high risk of system failure — something the site simply couldn’t afford during trading hours.
Initial inspection pointed towards a pressure control issue within the system.
Our Solution
We carried out a full inspection of the booster set and associated pipework, quickly identifying the root cause.
The non-return valve internals had completely failed, allowing system pressure to flow back into the tank. This reverse flow prevented the pump from achieving shut-off pressure, forcing it to run constantly.
Our engineers:
- Isolated the system safely
- Removed the failed non-return valve
- Installed a new correctly sized non-return valve
- Recommissioned the system and verified correct operation
Once installed, pressure control was immediately restored.
The Result
The booster set returned to normal operation, shutting down correctly once pressure was achieved and eliminating unnecessary strain on the pump.
✅ Correct system pressure restored
✅ Pump cycling returned to normal
✅ Reduced wear on pump components
✅ Improved reliability and efficiency
Why It Matters
Non-return valve failures are a common but often overlooked cause of pump issues. When left unchecked, they can lead to continuous running, higher running costs and avoidable breakdowns.
At NT Cloke Pumps & Water, we focus on accurate fault diagnosis, ensuring components are replaced only when necessary — keeping systems efficient, reliable and protected.
📞 0116 373 5496
📧 info@ntclokepumpsandwater.co.uk
You may also like
Location: LiverpoolService: Booster Set Upgrade & CAT 5 Water Tank InstallationSector: Residential / Apartment Block The Challenge Our engineers were
Location: UK (Commercial Site)Service: Bearing & Seal ReplacementSector: Commercial / Facilities Management The Challenge Our engineers were called to site
The Challenge Our engineers were called to a student accommodation block in Birmingham following reports of a noisy pump within
Location: BirminghamService: Pump & Inverter ReplacementSector: Student Accommodation / Residential The Challenge Our engineers were called to a large student
Location: UK (Commercial Site)Service: Pump Inspection, Safe Removal & RepairSector: Commercial / Facilities Management The Challenge The client contacted us
The brief NT Cloke Pumps & Water were instructed to carry out a full tank clean and chlorination on Tanks
The Call On Boxing Day, our team received an urgent call from one of our existing customers reporting no water
The Call-Out NT Cloke Pumps & Water were contacted by a commercial client after they noticed their heating pump had
Location: UKService: Domestic Booster Pump Fault Diagnosis & RepairSystem: DAB ESYBOXSector: Residential The Challenge The homeowner contacted us after experiencing
Location: RAF Base (UK)Service: Pump CommissioningEquipment: Grundfos Pump SystemSector: Defence / Critical Infrastructure The Challenge NT Cloke Pumps & Water
Location: Multiple Local SitesService: Pressurisation Unit Upgrades & Heating System ChecksSector: Commercial / Public Buildings The Challenge As the colder
Location: BirminghamService: Booster Set Replacement & System RepipeSector: Domestic / Residential The Challenge Following a full property refurbishment, the homeowner