Projects
Non-Return Valve Replacement – Restaurant, Cardiff City Centre
Location: Cardiff City Centre
Service: Non-Return Valve Replacement
Sector: Hospitality / Commercial
The Challenge
Our engineers were called to a busy restaurant in Cardiff city centre where a single pump booster set was running continuously and failing to shut down.
This constant operation was a clear warning sign. Left unresolved, it would have led to premature pump wear, increased energy use and a high risk of system failure — something the site simply couldn’t afford during trading hours.
Initial inspection pointed towards a pressure control issue within the system.
Our Solution
We carried out a full inspection of the booster set and associated pipework, quickly identifying the root cause.
The non-return valve internals had completely failed, allowing system pressure to flow back into the tank. This reverse flow prevented the pump from achieving shut-off pressure, forcing it to run constantly.
Our engineers:
- Isolated the system safely
- Removed the failed non-return valve
- Installed a new correctly sized non-return valve
- Recommissioned the system and verified correct operation
Once installed, pressure control was immediately restored.
The Result
The booster set returned to normal operation, shutting down correctly once pressure was achieved and eliminating unnecessary strain on the pump.
✅ Correct system pressure restored
✅ Pump cycling returned to normal
✅ Reduced wear on pump components
✅ Improved reliability and efficiency
Why It Matters
Non-return valve failures are a common but often overlooked cause of pump issues. When left unchecked, they can lead to continuous running, higher running costs and avoidable breakdowns.
At NT Cloke Pumps & Water, we focus on accurate fault diagnosis, ensuring components are replaced only when necessary — keeping systems efficient, reliable and protected.
📞 0116 373 5496
📧 info@ntclokepumpsandwater.co.uk
You may also like
Location: BirminghamClient: Large Leisure FacilityService: Mechanical Seal ReplacementSector: Commercial / Leisure The Challenge We were called to a large leisure
Location: BristolClient: University of BristolService: Booster Set Upgrade & Inverter ReplacementSector: Commercial / Education The Challenge We were called out
Location: Residential PropertyService: Tank Cleaning, Chlorination & Booster Set ServiceSector: Domestic The Challenge We were called to a residential property
Location: BirminghamService: Circulator Pump ReplacementSector: Commercial / Hotel The Challenge We were called to a hotel in Birmingham experiencing reduced
Location: Birmingham City CentreService: Booster Set UpgradeSector: Residential Apartment Block The Challenge We were called to an apartment block in
Location: Rural Property, ChippenhamService: Tank Cleaning, Chlorination & Booster Set ServiceSector: Domestic / Rural Water System The Challenge We attended
Location: Rural Property / FarmhouseService: Pump Installation & Tank CleaningSector: Domestic / Rural Water System The Challenge We were called
Location: BirminghamService: Ball Valve ReplacementSector: Residential / Apartment Block The Challenge During a routine service visit at a residential apartment
Location: Midlands (Apartment Block)Service: Booster Set Upgrade & ReplacementSector: Residential / Apartment Building The Challenge NT Cloke Pumps & Water
Location: BirminghamService: Booster Pump ReplacementSector: Residential / Apartment Block The Challenge NT Cloke Pumps & Water were called to a
Location: UK (Severn Trent Project Site)Service: Booster Set Upgrade & ReplacementSector: Industrial / Water Infrastructure The Challenge NT Cloke Pumps
Location: Birmingham (School)Service: Heating Pump UpgradeSector: Education / School Facility The Challenge NT Cloke Pumps & Water were scheduled to